RFQ

HRN3-80 — Voltage monitoring relays 3-Phase with selectable range

Brand

Supply

Supply Only

Genuinity

100% Genuine

Product Datasheet

Description

The HRN3-80 is a 3-phase voltage monitoring relay that protects connected equipment by monitoring undervoltage, phase loss, phase sequence, and phase asymmetry in 3-phase networks. Unlike fixed-range monitoring relays, the HRN3-80 offers a selectable monitoring range across a wide 208–480 V AC window, and its lower voltage threshold (Umin) is set as a percentage (80–95% of Un) of the selected range — making it adaptable to a variety of supply voltages commonly found across different installations and regions.

The relay is self-powered directly from the monitored circuit, eliminating the need for a separate control supply. It measures true RMS voltage for accurate monitoring even under distorted waveforms, and features an adjustable time delay (0.3–30 s) to ride through brief voltage dips without nuisance tripping. Phase asymmetry monitoring is adjustable (2–10% of Un) and can be switched off entirely if not required. Clear LED indication on the front panel shows supply status and fault conditions, making diagnostics straightforward for panel builders and maintenance technicians protecting motors, pumps, and other 3-phase loads from voltage-related damage.

Technical Specification

Attribute Value
Supply/monitored terminals L1-L2-L3
Supply/monitored voltage AC 3× 208–480 V (50–60 Hz)
Consumption (max.) 2 VA/1 W
Range setting Adjustable
Lower level setting (Umin) 80–95% Un
Asymmetry setting Adjustable 2–10% Un + OFF
Max. permanent voltage AC 3× 550 V
Peak overload (1 s) AC 3× 600 V
Time delay (t1) 2 s (fixed)
Time delay (t2) Adjustable 0.3–30 s

Accuracy

Attribute Value
Setting accuracy (mech.) 5%
Repeat accuracy <1%
Temperature dependency <0.1%/°C
Hysteresis (fault to OK) 5%

Output

Attribute Value
Contact type 1× changeover / SPDT (AgNi)
Current rating 16 A/AC1; 1 HP @240Vac, ½ HP @120Vac; PD.B300
Breaking capacity 4000 VA/AC1, 384 W/DC1
Switching voltage 250 V AC / 24 V DC
Power dissipation (max.) 1.2 W
Mechanical life 10,000,000 ops
Electrical life (AC1) 100,000 ops

Environmental & Other

Attribute Value
Operating temperature −20°C to +55°C
Storage temperature −30°C to +70°C
Dielectric strength AC 4 kV (supply–output)
Protection degree IP40 (front panel) / IP20 (terminals)
Overvoltage category III
Pollution degree 2
Max. cable size 1×2.5 or 2×1.5 mm² solid / 1×2.5 mm² (AWG 14) with ferrule
Dimensions 90 × 52 × 66 mm
Weight 66 g
Standards EN 60255-1, EN 60255-26, EN 60255-27

Related Products