RFQ

KFD2-SR2-Ex2.W — Switch Amplifier, 2-Channel Isolated Barrier, Relay Output, SIL 2

Supply

Supply Only

Genuinity

100% Genuine

Product Datasheet

Description

The KFD2-SR2-Ex2.W is a 2-channel isolated switch amplifier (barrier) from Pepperl+Fuchs’s K-System range, designed for intrinsic safety applications where signals need to be safely transferred between a hazardous area and a non-hazardous control area. It accepts digital input signals from NAMUR proximity sensors or dry (volt-free) mechanical contacts in Zone 0/1/2 or Division 1/2 hazardous locations, and converts them into isolated relay contact outputs for the control side.

Each of the two independent channels provides a changeover relay output that switches state whenever its corresponding input signal changes, and the normal output state of each channel can be reversed individually via onboard DIP switches (S1, S2) to suit the application logic. A separate switch (S3) enables or disables line fault detection (LFD), which monitors the field wiring for breakage or short-circuit and reverts the relay to its de-energized (safe) state on a fault condition, with LED indication per NAMUR NE 44. The device is powered via 24V DC, either through a Power Rail system (which also enables a collective error message) or directly via terminals. Rated up to SIL 2 (SC 3) per IEC/EN 61508, it’s well suited for level, flow, and proximity switch monitoring in hazardous-area process plants, including oil & gas, petrochemical, and marine/offshore installations.

Technical Specification

Attribute Value
Signal type Digital Input
Number of channels 2-channel isolated barrier
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3

Supply

Attribute Value
Connection Power Rail or terminals 14+, 15−
Rated voltage (Ur) 19–30 V DC
Ripple ≤10%
Rated current (Ir) ≤50 mA
Power dissipation ≤1 W
Power consumption ≤1 W

Input (Field Side)

Attribute Value
Connection Terminals 1+, 2+, 3−; 4+, 5+, 6−
Rated values Per EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current ~8V DC / ~8 mA
Switching point/hysteresis 1.2–2.1 mA / ~0.2 mA
Line fault detection Breakage I≤0.1mA, short-circuit I>6mA
Pulse/Pause ratio Min. 20 ms / min. 20 ms

Output (Control Side)

Attribute Value
Connection Output I: terminals 7,8,9 / Output II: terminals 10,11,12
Output type Signal, relay
Contact loading 250V AC/2A/cosφ>0.75; 126.5V AC/4A/cosφ>0.75; 40V DC/2A resistive
Minimum switch current 2 mA / 24V DC
Energized/de-energized delay ~20 ms / ~20 ms
Mechanical life 10⁷ switching cycles
Collective error message Via Power Rail
Switching frequency ≤10 Hz

Galvanic Isolation

Attribute Value
Input/Output, Input/Supply, Output/Supply, Output/Output Reinforced insulation per IEC/EN 61010-1, rated 300 Veff

Indicators & Settings

Attribute Value
Display elements LEDs
Control elements DIP switch
Configuration Via DIP switches

Environmental & Mechanical

Attribute Value
Ambient temperature −40°C to 70°C
Degree of protection IP20
Connection Screw terminals
Mass ~150 g
Dimensions (W×H×D) 20 × 119 × 115 mm
Mounting 35mm DIN rail (EN 60715)

Hazardous Area / Ex Data

Attribute Value
EU-type examination certificate PTB 00 ATEX 2080
Marking II (1)G [Ex ia Ga] IIC / II (1)D [Ex ia Da] IIIC / I (M1) [Ex ia Ma] I
Input Ex ia Uo 10.5V, Io 13mA, Po 34mW (linear)
Max safe voltage (supply) 253V AC / 125V DC
Max safe voltage (output) 253V AC
Certificate (ic) PF 08 CERT 0803
IECEx certificate IECEx PTB 11.0034, IECEx TUN 19.0013X

Standards & Certification

Attribute Value
Directive conformity 2014/30/EU (EMC), 2014/35/EU (LVD), 2014/34/EU (ATEX)
Functional safety IEC/EN 61508:2010
International approvals FM (FM19US0207X), UL (E106378, cULus)
HS/Commodity code 8536 5019