RFQ

HRN-100/2 — Multifunction voltage/frequency monitoring relay in 3P with LCD display

Brand

Supply

Supply Only

Genuinity

100% Genuine

Product Datasheet

Description

The HRN-100/2 is a multifunction voltage/frequency monitoring relay for 3-phase networks, featuring a backlit LCD display for easy configuration and real-time monitoring. It supports both 3-wire and 4-wire (with or without neutral) connections and can be configured to monitor upper and lower voltage thresholds, frequency, phase sequence, phase failure, and phase asymmetry (including neutral fail on 4-wire setups). The device is self-powered from the monitored voltage and measures true RMS AC voltage for accurate readings under non-sinusoidal conditions.

Both output relays (RL1 and RL2) can be configured independently, each with adjustable response delays (Pon, Ton, Toff) and a choice of Fail Safe or Non Fail Safe operation. A fault-memory function allows automatic or manual reset from a fault state, and the last five fault events are logged and retrievable from the display history. The transparent front cover can be sealed to protect settings from unauthorized changes, making the HRN-100/2 well suited for protecting motors, pumps, compressors, and other 3-phase equipment from damage caused by voltage anomalies.

Technical Specification

Attribute Value
Product type Multifunction voltage/frequency monitoring relay, 3-phase
Connection 3-wire or 4-wire (with/without neutral)
Display Backlit LCD
Mounting DIN rail (EN 60715)
Dimensions 90 × 36 × 66.5 mm
Weight 132 g

Supply

Attribute Value
Supply/monitored terminals L1-L2-L3 (N)
Supply/monitored voltage Phase (ULN): 90–288 V AC · Line (ULL): 155–500 V AC (45–65 Hz)
Consumption (max.) 5 VA

Measuring

Attribute Value
Measured circuit selection Phase voltage (3-phase, 4-wire) or line voltage (3-phase, 3-wire)
Adjustable OV/UV thresholds Phase: 90–288 VAC · Line: 155–500 VAC
Upper/lower limit voltage (HC/LC) Phase: 310 VAC / 85 VAC · Line: 535 VAC / 150 VAC
Adjustable frequency levels (OF/UF) 45–65 Hz
Adjustable asymmetry Absolute: 5–99 VAC · Percentage: 2–50%
Voltage/frequency hysteresis 3–20 VAC (OV, UV, HC, LC) · 0.5–2 Hz (OF, UF)
Asymmetry hysteresis Absolute: 3–99 VAC · Percentage: 2–15%
Voltage measurement accuracy ±5 V
Frequency measurement accuracy ±0.3 Hz
Delay after supply connection (Pon) 0–999 s
Delay Ton / Toff 0.5–999 s / 0.1–999 s
Fixed delay <100 ms (phase sequence, failure) · <200 ms (HC, LC) · <500 ms (neutral fail)

Output

Attribute Value
Contact type 2× changeover (AgSnO₂)
Current rating 5 A / AC1
Breaking capacity 1200 VA/AC1, 150 W/DC1
Switching voltage 240 V AC / 30 V DC
Power dissipation (max.) 5 W
Mechanical life 10,000,000 operations
Electrical life (AC1) 100,000 operations

Environmental & Other

Attribute Value
Operating temperature −10 to +60 °C
Storage temperature −20 to +70 °C
Dielectric strength AC 4 kV (supply–output)
Protection degree IP20 (housing/terminals), IP40 (front panel with cover)
Overvoltage category III
Pollution degree 2
Cross-wire section max. 1×2.5 / 2×1.5 mm² (solid/stranded with ferrule)
Standards EN 60255-1, EN 60255-26, EN 60255-27