RFQ

KFD2-STC5-Ex2 — SMART Transmitter Power Supply, 2-Channel Isolated Barrier, SIL 2

Supply

Supply Only

Genuinity

100% Genuine

Product Datasheet

Description

The KFD2-STC5-Ex2 is a 2-channel isolated barrier from Pepperl+Fuchs’s K-System range, purpose-built to power and interface with SMART transmitters in intrinsic safety applications. It supplies loop power to 2-wire and 3-wire SMART transmitters located in Zone 0/1/2 or Division 1/2 hazardous areas, and can also work with 2-wire SMART current sources — transferring the 0/4–20mA analog signal through to the safe-area control side as an isolated current value.

A key feature of this barrier is its bidirectional digital communication support: superimposed HART, BRAIN, or Foxboro digital signals on the input loop are transferred transparently between the hazardous and safe areas, so smart-transmitter configuration and diagnostics tools can be used without extra wiring. Each channel’s safe-area output can be independently configured for current sink or current source mode, giving flexibility to match different DCS/PLC input card requirements. Removable terminals with integrated HART communicator test points simplify commissioning and maintenance, and an internal resistor is available for applications where the control-circuit HART communication resistance is too low. Powered via 24V DC through the Power Rail system, and rated up to SIL 2 (per IEC/EN 61508), the KFD2-STC5-Ex2 is well suited for pressure, level, flow, and temperature transmitter signal conditioning in hazardous-area process plants, including oil & gas, petrochemical, and marine/offshore installations.

Technical Specification

Attribute Value
Signal type Analog input
Number of channels 2-channel isolated barrier
Safety Integrity Level (SIL) SIL 2
SMART protocols supported HART, BRAIN, Foxboro

Supply

Attribute Value
Connection Power Rail or terminals 14+, 15−
Rated voltage (Ur) 18–30 V DC
Ripple Within supply tolerance
Power dissipation ≤1.4 W at max load
Power consumption ≤2.6 W at max load

Input (Field Side)

Attribute Value
Connection Terminals 1+, 2−, 3; 4+, 5−, 6
Input signal 0/4–20 mA
Available voltage ≥16 V at 20mA (terminals 1+,3 / 4+,6)

Output (Control Side)

Attribute Value
Connection Terminals 7+,8−,9− / 10+,11−,12− (sink) or 7−,8+,9+ / 10−,11+,12+ (source)
Load 0–600 Ω
Output signal 0/4–20 mA (overload >25 mA)
Ripple ≤50 µA rms

Transfer Characteristics

Attribute Value
Deviation at 20°C ≤10 µA (incl. calibration, linearity, hysteresis, load & supply fluctuation)
Ambient temperature influence ≤0.25 µA/K
Frequency range (field→control) 0–7.5 kHz (−3dB), 1Vpp signal
Frequency range (safe→hazardous) 0.3–7.5 kHz (−3dB), 1Vss signal
Settling time 200 µs
Rise/fall time 100 µs

Galvanic Isolation

Attribute Value
Output/Power supply Functional insulation, 50V AC rated
Output/Output Functional insulation, 50V AC rated

Indicators & Mechanical

Attribute Value
Display elements LED (green — power supply)
Degree of protection IP20
Connection type Screw terminals (removable)
Mass ~200 g
Dimensions (W×H×D) 20 × 124 × 115 mm
Mounting 35mm DIN rail (EN 60715)
Ambient temperature −20°C to 60°C

Hazardous Area / Ex Data

Attribute Value
EU-type examination certificate CML 17 ATEX 2031 X
Marking II (1)G [Ex ia Ga] IIC / II (1)D [Ex ia Da] IIIC / I (M1) [Ex ia Ma] I
Max safe voltage (supply) 250 V
Input Ex ia (1+,3−/4+,6−) Uo 26.2V, Uq 27.25V, Io 93mA, Po 634mW
Input Ex ia (2−,3+/5−,6+) Ui 30V, Ii 115mA, Pi 1W, Uo 2V, Io 8.5mA, Po 4.3mW
Certificate (ec) CML 17 ATEX 3030 X — II 3G Ex ec IIC T4 Gc
IECEx certificate IECEx CML 17.0016X
Galvanic isolation (Ex) Input/Output & Input/Supply: 375V peak (IEC/EN 60079-11)

Standards & Certification

Attribute Value
Directive conformity 2014/30/EU (EMC), 2014/34/EU (ATEX)
EMC standards EN 61326-1, EN 61326-3-2, NE 21
International approvals UL (control drawing pending), IECEx CML 17.0016X
HS/Commodity code 8543 7090